25
52
I
Closing
request
Closing
command
GUID-2AF445C8-388A-42DF-B5B3-070C34F3C7AB V2 EN
Figure 262:
A simplified block diagram of 25 in the command mode operation
The closing signal is delivered only once for each activated external closing command
signal. The pulse length of the delivered closing is set with the
Close pulse
setting.
t = Close pulse
GUID-0D9A1A7F-58D1-4081-B974-A3CE10DEC5AF V2 EN
Figure 263:
Determination of the pulse length of the closing signal
In the command control mode operation, there are alarms for a failed closing attempt
(
CL_FAIL_AL
) and for a command signal that remains active too long
(
CMD_FAIL_AL
).
If the conditions for closing are not fulfilled within the set time of
Maximum Syn time
, a
failed closing attempt alarm is given. The
CL_FAIL_AL
alarm output signal is pulse-
shaped and the pulse length is 500 ms. If the external command signal is removed too
early, that is, before conditions are fulfilled and the closing pulse is given, the alarm timer
is reset.
Section 9
1MRS240050-IB C
Control functions
502
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...