In case 1, the reset is delayed with the
Reset delay time
setting and in case 2, the counter
is reset immediately, because the
Reset delay time
setting is set to zero.
A070421-ANSI V1 EN
Figure 294:
Drop-off period is longer than the set Reset delay time
When the drop-off period is longer than the set
Reset delay time
, as described in
, the input signal for the definite timer (here: timer input) is active, provided that the
current is above the set
Pickup value
. The input signal is inactive when the current is below
the set
Pickup value
and the set hysteresis region. The timer input rises when a fault current
is detected. The definite timer activates the
PICKUP
output and the operation timer starts
elapsing. The reset (drop-off) timer starts when the timer input falls, that is, the fault
disappears. When the reset (drop-off) timer elapses, the operation timer is reset. Since this
happens before another pickup occurs, the
TRIP
output is not activated.
Section 12
1MRS240050-IB C
General function block features
568
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...