8-58
8-6 Extended Parameters
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
8
Parameters Details
Explanation of Set Values
Set the detection of Err28.0 "pulse regeneration error".
Explanation of Set Values
Set the operation limits for the front panel.
The operation limits depend on the mode. The operation limits are as follows.
Pn533
Pulse Regeneration Output Limit Setting
Setting
range
0 to 1
Unit
−
Default
setting
Power OFF
and ON
Yes
All
Set
value
Explanation
0
Error detection disabled
1
Error detection enabled
Pn535
Front Key Protection Setting
Setting
range
0 to 1
Unit
−
Default
setting
Power OFF
and ON
Yes
All
Set
value
Explanation
0
Front panel operation not limited
1
Front panel operation limited
Mode
Operation limits
MONITOR mode
All monitor data can be checked.
PARAMETER SETTING mode Parameters cannot be changed. However, parameter set values can
be checked.
EEPROM WRITE mode
Cannot be executed. (Will not be displayed)
AUXILIARY FUNCTION mode
Operations other than the release of the front key protection setting
cannot be executed. (Will not be displayed)