4-3 Wiring Conforming to EMC Directives
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
4
System Design
Leakage Breaker
Select leakage breakers designed for protection against ground faults.
Because switching takes place inside the drivers, high-frequency current leaks from the SW
elements of the driver, the armature of the motor, and the cables.
High-frequency, surge-resistant leakage breakers, because they do not detect high-frequency
current, can prevent operation with high-frequency leakage current.
When using a general leakage breaker, use 3 times the total of the leakage current given in the
following table as a reference value.
When selecting leakage breakers, remember to add the leakage current from devices other than
the motor, such as machines using a switching power supply, noise filters, inverters, and so on.
To prevent malfunction due to inrush current, we recommend using a leakage breaker of 10 times
the total of all current values.
The leakage breaker is activated at 50% of the rated current. Allow leeway when selecting a
leakage breaker.
For details on leakage breakers selection method, refer to the manufacturer's catalog.
Driver model
Inrush current (Ao-p)
Main circuit
power supply
Control circuit
power supply
R88D-KT06F
28
48
R88D-KT10F
28
48
R88D-KT15F
28
48
R88D-KT20F
32
48
R88D-KT30F
32
48
R88D-KT50F
32
48