143
Local I/O Settings
Section 5-5
5-5-2
Setting Safety Inputs
Click the
Local IN/Test Output
Tab and then click the
General
Tab in the win-
dow. To configure the safety inputs.
Note
There are many settings for safety inputs. The display window is thus
separated into the General Tab Page and On-Off Delay/Discrepancy
Time Tab Page. Safety input scan are set from both tab pages.
Error Latch Time
This parameter applies to all safety inputs and test outputs. It sets the time to
latch the error state when an error occurs in an input or output.
Even if cause of the cause of the error has been removed, the error state is
always latched for this time. It can be set between 0 and 65,530 ms in 10-ms
increments.
Settings for Individual Safety Inputs
Double-click the row of the safety input to set or select the row and click the
Edit
Button.