315
Appendix A
4.
Target node IDs are assigned to devices registered in the Register Device List. This target node ID deter-
mines the location in the originator node PLC of the Target Node PLC Operating Flag, Target Node PLC
Error Flag, Registered Target Node Flag, and Normal Target Node Flag. By default, the target ID is auto-
matically set to the rightmost 8 bits of the IP address. In the example above, the target device’s IP address
is 192.168.250.2, so the device number is #002. If a target node ID is duplicated and you want to change
the device number, click the
Change Target Node ID
Button and change the target ID.
Connections Settings (Editing All Connections)
The connection settings between the originator and all of the target devices selected in the Register Device List
can be edited together in a table. (There is another method in which connections are edited individually.)
1.
Select the
Connections
Tab, and click the
Edit All
Button. The following Edit All Connections Dialog Box
will be displayed.
The following table describes the various settings in the dialog box.
Setting
Function
Target Device
Selects the target device.
Connection
Name
Any name can be given to the connection (up to 32 characters).
If this field is left blank, a default name will be assigned.
This Connection Name can be used for comments.
Connection I/O
Type
When making tag data links in a CS1W-EIP21 or CJ1W-EIP21, select
Input Only (Tag type)
.
When making tag data links in other devices, select the connection I/O type specified in that
device’s EDS file.
Use the
Input Only (ID type)
setting when another company’s node is the originator and does not
support connection settings with the
Tag type
setting.
In/Out
The connections I/O is automatically displayed based on the selected connection.
• Input Only: Just
In
is displayed.
• Output Only: Just
Out
is displayed.
• Output & Input:
In
and
Out
are displayed in two levels.
Summary of Contents for DeviceNet Safety
Page 1: ...SYSTEM CONFIGURATION MANUAL Cat No Z905 E1 07 DeviceNet Safety...
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ...DeviceNet Safety System Configuration Manual Revised July 2009...
Page 6: ...iv...
Page 11: ...ix TABLE OF CONTENTS Appendix 277 Glossary 333 Index 335 Revision History 339...
Page 12: ......
Page 14: ...xii...
Page 18: ...xvi...
Page 68: ......
Page 122: ......
Page 167: ...133 Safety Slave Settings Section 5 2...
Page 234: ......
Page 266: ......
Page 366: ......
Page 372: ......
Page 374: ......
Page 375: ......