150
Setting the Operating Mode and Confirming the Cycle Time
Section 5-6
IMPORTANT
•
When disabling DeviceNet communications, connect the Network Configu-
rator via the NE1A-series Controller’s USB port. If the parameters that dis-
abled DeviceNet communications are downloaded while connected via a
DeviceNet Interface Card, an error will occur in the Network Configurator
because the DeviceNet communications of the NE1A-series Controller will
stopped.
•
With NE1A-series Controllers that support EtherNet/IP, it is possible to con-
nect via EtherNet/IP.
5-6-2
Confirming the Cycle Time
Cycle Time
The NE1A-series Controller cycle time is automatically calculated and dis-
played based on the set parameters and programs created in the Logic Editor.
The cycle time is used in calculating the reaction time and the ON/OFF delay
time settings. Check the value after all the parameters and programs have
been set.
I/O Refresh Cycle
The I/O refresh cycle is used to refresh local I/O. It is automatically calculated
with the cycle time and displayed.
The I/O refresh cycle time is used in calculating the reaction time.
Check the value after all the parameters and programs have been set.
Summary of Contents for DeviceNet Safety
Page 1: ...SYSTEM CONFIGURATION MANUAL Cat No Z905 E1 07 DeviceNet Safety...
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ...DeviceNet Safety System Configuration Manual Revised July 2009...
Page 6: ...iv...
Page 11: ...ix TABLE OF CONTENTS Appendix 277 Glossary 333 Index 335 Revision History 339...
Page 12: ......
Page 14: ...xii...
Page 18: ...xvi...
Page 68: ......
Page 122: ......
Page 167: ...133 Safety Slave Settings Section 5 2...
Page 234: ......
Page 266: ......
Page 366: ......
Page 372: ......
Page 374: ......
Page 375: ......