144
Local I/O Settings
Section 5-5
Terminal Name
A terminal name can be set for a safety input. The terminal name set here is
used as the I/O tag in the Logic Editor.
Channel Mode
Set the Channel Mode for the safety input.
Channel Mode
Description
Not Used
The corresponding safety input will not be used. (It does not connect to an exter-
nal input device.)
Test pulse from test out
Specifies connecting a device with a contact output in combination with a test out-
put.
When this mode is selected, select the test output to use for the
Test Source
and
then set the test output mode to
Pulse Test Output
.
When these settings are made, contact between the input signal line and the
power supply (plus) and short circuits with other input signal lines can be
detected.
Used as safety input
Specifies connecting a safety device with a semiconductor output, such as a light
curtain.
Used as standard input
Specifies connecting a standard device (i.e., a non-safety device).
Summary of Contents for DeviceNet Safety
Page 1: ...SYSTEM CONFIGURATION MANUAL Cat No Z905 E1 07 DeviceNet Safety...
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ...DeviceNet Safety System Configuration Manual Revised July 2009...
Page 6: ...iv...
Page 11: ...ix TABLE OF CONTENTS Appendix 277 Glossary 333 Index 335 Revision History 339...
Page 12: ......
Page 14: ...xii...
Page 18: ...xvi...
Page 68: ......
Page 122: ......
Page 167: ...133 Safety Slave Settings Section 5 2...
Page 234: ......
Page 266: ......
Page 366: ......
Page 372: ......
Page 374: ......
Page 375: ......