223
Connection Status Tables
Section 8-1
01:0114
Vendor ID or Product Code
Error
The device data (vendor ID or product code) for the device on the Configurator
and the device used in the actual system does not match.
• Use Safety Slave Verification (
Device - Parameter - Verify
) to check that the
device in the system and the device registered to the Safety Master match.
• If they do match, delete then re-register the connections registered to the
Safety Master.
01:0115
Device Type Error
The device data (device type) for the device on the Configurator and the device
used in the actual system does not match.
• Use Safety Slave Verification (
Device - Parameter - Verify
) to check that the
device in the system and the device registered to the Safety Master match.
01:0116
Firmware Revision Error
The device data (firmware revision) for the device on the Configurator and the
device used in the actual system does not match.
• Use Safety Slave Verification (
Device - Parameter - Verify
) to check that the
device in the system and the device registered to the Safety Master match.
• If they do match, delete then re-register the connections registered to the
Safety Master.
01:0117
Connection Path Error
Two ore more single-cast safety I/O connections or a multi-cast safety I/O con-
nection with a different EPI has been set for a safety slave I/O.
• To share one safety slave I/O on a Safety Slave with more than one Safety
Master, make the EPI all the same and set the connection type to Multi-cast.
• NE1A-series Controller Safety Slaves cannot have more than one single-cast
safety I/O connection for each Safety Slave I/O. Set multiple connection paths
for the NE1A-series Safety Slave Safety Slave I/O.
• If the connection is not restored with the above remedy, delete then re-regis-
ter the connections registered to the Safety Master.
01:031E
No. of Connections Error
The setting for the number of safety I/O connections exceeds the upper limit
supported by the Safety Slave. Adjust the Safety Connection setting for the rel-
evant Safety Master. In particular, check that no more than 15 Safety Masters
are set for each Multi-cast connection, with a maximum total of 60.
01:031F
Connection ID Resource
Error
The maximum number of connection IDs for one Safety Master (12) has been
exceeded.
Change the ID allocation under
Edit Safety Connection – Expansion Con-
nection Setting
to “Check Produced IDs in the Safety Slave” in the corre-
sponding Safety I/O Connection (Safety Input Assembly) setting, then
download the device parameters to the Safety Master again.
01:07FF
Non-existent Safety Slave
The Safety Slave may not have been added to the network correctly. Check
that the corresponding Safety Slave is online (i.e., the NS indicator is flashing
green or lit green.) If the Safety Slave is not online, check the following items.
• Is the node address for the Safety Slave correct?
• Do all nodes have the same baud rate?
• Is the cable length correct (trunk lines and branch lines)?
• Is the cable disconnected or slack?
• Is the terminating resistance only on both ends of the main line?
• Is there a lot of noise?
01:080C
Safety Signature Mismatch The safety signature for the Safety Slave monitored by the Safety Master does
not match the safety signature of the Safety Slave itself.
• Reset the Safety Slave to default settings then download the device parame-
ters again.
• If the above remedy does not work, delete then re-register the connections
registered to the Safety Master.
01:080E
TUNID Mismatch
The TUNID for the Safety Slave monitored by the Safety Master does not
match the TUNID of the Safety Slave itself.
• Reset the Safety Slave to default settings then download the correct device
parameters.
• If the above remedy does not work, delete then re-register the connections
registered to the Safety Master.
Refer to
3-4-2 Network Numbers
for information on TUNIDs.
Status
Countermeasure
Summary of Contents for DeviceNet Safety
Page 1: ...SYSTEM CONFIGURATION MANUAL Cat No Z905 E1 07 DeviceNet Safety...
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ...DeviceNet Safety System Configuration Manual Revised July 2009...
Page 6: ...iv...
Page 11: ...ix TABLE OF CONTENTS Appendix 277 Glossary 333 Index 335 Revision History 339...
Page 12: ......
Page 14: ...xii...
Page 18: ...xvi...
Page 68: ......
Page 122: ......
Page 167: ...133 Safety Slave Settings Section 5 2...
Page 234: ......
Page 266: ......
Page 366: ......
Page 372: ......
Page 374: ......
Page 375: ......