125
Safety Connection Settings
Section 5-1
Stop only the connection where
the error occurred.
Specify this mode to keep safety I/O communications with a safety slave stopped
after a safety I/O communications error has occurred with the slave.
To restart safety I/O communications with the safety slave after I/O communica-
tions have been stopped, use the Network Configurator to send a command to
restart communications. It is also possible to write a logic routine in the logic pro-
gram in advance to turn ON the Safety I/O Communications Restart Flag and
restart communications with a specified trigger bit.
Stop all connections
Specify this mode to stop safety I/O communications with all safety slaves
stopped after a safety I/O communications error has occurred.
To restart safety I/O communications with the safety slaves after I/O communica-
tions have been stopped, use the Network Configurator to send a command to
restart communications. It is also possible to write a logic routine in the logic pro-
gram in advance to turn ON the Safety I/O Communications Restart Flag and
restart communications with a specified trigger bit.
This function is enabled when normal safety I/O communications are established
with all Safety Slaves.
Mode after
communications error
Description
Summary of Contents for DeviceNet Safety
Page 1: ...SYSTEM CONFIGURATION MANUAL Cat No Z905 E1 07 DeviceNet Safety...
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ...DeviceNet Safety System Configuration Manual Revised July 2009...
Page 6: ...iv...
Page 11: ...ix TABLE OF CONTENTS Appendix 277 Glossary 333 Index 335 Revision History 339...
Page 12: ......
Page 14: ...xii...
Page 18: ...xvi...
Page 68: ......
Page 122: ......
Page 167: ...133 Safety Slave Settings Section 5 2...
Page 234: ......
Page 266: ......
Page 366: ......
Page 372: ......
Page 374: ......
Page 375: ......