16. Starting the Network Configurator and Connecting to the Network
Start the Network Configurator and connect it to the network via the USB
port on the NE1A-series Controller or via DeviceNet or EtherNet/IP.
Refer to
3-3 Connecting to the Network.
17. Reading the Network Configuration File
Read the saved network configuration file with the completed design
changes.
Refer to
3-5-3 Reading a Network Configuration File.
18. Downloading Device Parameters
Download the parameters to all the devices.
Refer to
3-7-3 Downloading Device Parameters.
19. Confirming the Downloaded Device Parameters and Safety Signature
Verify the parameters for all devices with an icon indicating pre-verification
and check if the device parameters and program that the user input are
correctly downloaded and saved to the devices.
Refer to
3-8 Parameter Verification.
20. Saving the Network Configuration File
Save the configuration file for a network in which parameter verifications of
all the devices have been completed.
Refer to
3-5-2 Saving the Network Configuration File.
21. Exiting the Network Configurator
Exit the Network Configurator.
IMPORTANT
• After downloading the device parameters, verify the parameters to con-
firm that the parameters and the safety signature saved in the device are
correct.
• When selecting
Open Only
in the Open Type setting for the safety con-
nection, check that the Safety Master and Safety Slave are correctly con-
figured.
Note
•
In the Network Configuration Pane, the device will be displayed as
locked, but the actual device has already been unlocked. Therefore, the
parameters can be downloaded.
•
If downloading to a device with a key icon color that has changed to yel-
low because of parameter changes, the icon must be returned to the state
before verification (white [ S ] symbol).
• If downloading to a device with a key icon color that has not changed
because parameters have not been changed, the icon must be returned
to the state indicating that verification has been completed (green [ S ]
symbol).
Additional User Testing
22. User Testing
The user himself must verify device parameters and operation to confirm
that the safety system requirement specifications are met.
23. Starting the Network Configurator and Connecting to the Network
Summary of Contents for DeviceNet Safety
Page 1: ...SYSTEM CONFIGURATION MANUAL Cat No Z905 E1 07 DeviceNet Safety...
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ...DeviceNet Safety System Configuration Manual Revised July 2009...
Page 6: ...iv...
Page 11: ...ix TABLE OF CONTENTS Appendix 277 Glossary 333 Index 335 Revision History 339...
Page 12: ......
Page 14: ...xii...
Page 18: ...xvi...
Page 68: ......
Page 122: ......
Page 167: ...133 Safety Slave Settings Section 5 2...
Page 234: ......
Page 266: ......
Page 366: ......
Page 372: ......
Page 374: ......
Page 375: ......