269
Resetting a Device
Section 9-12
9-12 Resetting a Device
This section describes how to reset a Safety Device.
9-12-1 Reset Types
The following three methods can be used to reset a Safety Device.
The Safety Device saves the following configuration information in nonvolatile
memory.
The information above is saved in nonvolatile memory in the device. It will not
be cleared by restarting the power supply. To clear the information (to return
to the default settings), select the
Reboot and reset configuration
or
Reboot
and reset configuration without
... Option when resetting.
Reset type
Description
Reboot
This is the same as turning the power OFF and ON.
Reboot and reset
configuration
All configuration information saved in the device's nonvolatile
memory will be returned to the default values and the device
will be restarted.
Reboot and reset
configuration with-
out specified items
All configuration information in the device's nonvolatile mem-
ory other than specified items will be returned to the default
values and the device will be restarted.
Type
Default
setting
Set when
Description
Node address
(software setting)
63
Node address is
changed.
The node address at startup
when software settings are
enabled.
Baud rate (soft-
ware setting)
125 Kbit/s
Baud rate is
changed
The baud rate at startup when
the software settings are
enabled (NE1A-series Con-
troller only).
TUNID (Target
Unique Node Iden-
tifier)
Not set
First time parame-
ters are down-
loaded.
The identifier of the local node
in the Safety Network consist-
ing of the network number
and node address.
Password
No pass-
word
Password is
changed.
The password for the device.
CFUNID (Configu-
ration Owning
UNID)
Not set
First time parame-
ters are down-
loaded.
The UNID of the configuration
source.
OCPUNID (Output
Connection Point
Owning UNID)
Not set
First time safety
communications
are started.
The UNID of the Safety Mas-
ter that opens a safety output
connection.
Summary of Contents for DeviceNet Safety
Page 1: ...SYSTEM CONFIGURATION MANUAL Cat No Z905 E1 07 DeviceNet Safety...
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ...DeviceNet Safety System Configuration Manual Revised July 2009...
Page 6: ...iv...
Page 11: ...ix TABLE OF CONTENTS Appendix 277 Glossary 333 Index 335 Revision History 339...
Page 12: ......
Page 14: ...xii...
Page 18: ...xvi...
Page 68: ......
Page 122: ......
Page 167: ...133 Safety Slave Settings Section 5 2...
Page 234: ......
Page 266: ......
Page 366: ......
Page 372: ......
Page 374: ......
Page 375: ......