226
Errors When Downloading
Section 8-2
The error occurred in the validation of a
device parameter.
There is a non-alignment between configuration parameters. Check the
following items and change the parameters.
• The time parameters (e.g., Discrepancy Time) set for function blocks in
the NE1A-series Controller settings are shorter than the NE1A-series
Controller cycle time.
• The safety connection EPI is shorter than the cycle time.
• The safety inputs are set to
Test pulse from test out
but the test source
has not been set.
• One of the safety inputs in a dual channel setting is set as a standard
input and the other has a different setting.
• One of the safety inputs in a dual channel setting is set to
Not Use
and
the other has a different setting.
• One of the safety outputs in a dual channel setting is set to
Not Use
and
the other has a different setting.
• The maximum number of connection IDs for one Safety Master (12) has
been exceeded in the safety I/O configuration. Change the ID allocation
under
Edit Safety Connection - Expansion Connection Setting
to
“Check Produced IDs in the Safety Slave” in the corresponding Safety I/O
Connection (Safety Input Assembly) setting, then download the device
parameters to the Safety Master again.
The program may have been created with an earlier Network Configurator
than version 1.5
@
. The checks for safety functions have been improved in
version 1.5
@
so programs created in an earlier version of the NE1A-series
Controller cannot be downloaded as is. Use the following procedure to
convert the program and then download the program again.
1. Click the
Edit
Button on the Logic Tab page in the Edit Device Parame-
ters Window of the NE1A-series Controller to open the Logic Editor.
2. Select
Edit – Find Function Blocks with Open Connections
to check
all function block I/O are connected. For information on open function
block connections, refer to
Precautions Updating from Network Configu-
rator Version 1.3@ to a Higher Version
on page xxxi.
3. Select
File – Apply
to save the logic program then close the Logic Editor.
4. Return to the NE1A-series Controller’s Edit Device Parameters Window
and click the
OK
Button.
The hardware may be malfunctioning. Cycle the NE1A-series Controller
power and execute self-diagnosis. If the MS indicator is lit red, replace the
hardware.
Logic Editor: Consistency Error.
The network configuration has changed, which has resulted in a non-align-
ment between the logic program data and other data. Start Logic Editor
and check changed I/O locations and make the settings again.
Device can not be accessed.
Device is waiting for a TUNID setting (NS indicator is flashing green/red)
after reset was executed from another node during download. Set the
TUNID and download again.
Refer to
3-4-2 Network Numbers
for information on TUNIDs.
With Controllers that support EtherNet/IP, use the DeviceNet Network Win-
dow for downloads. Downloads cannot be executed from the EtherNet/IP
Network Window.
Message displayed on the Network
Configurator
Countermeasure
Summary of Contents for DeviceNet Safety
Page 1: ...SYSTEM CONFIGURATION MANUAL Cat No Z905 E1 07 DeviceNet Safety...
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ...DeviceNet Safety System Configuration Manual Revised July 2009...
Page 6: ...iv...
Page 11: ...ix TABLE OF CONTENTS Appendix 277 Glossary 333 Index 335 Revision History 339...
Page 12: ......
Page 14: ...xii...
Page 18: ...xvi...
Page 68: ......
Page 122: ......
Page 167: ...133 Safety Slave Settings Section 5 2...
Page 234: ......
Page 266: ......
Page 366: ......
Page 372: ......
Page 374: ......
Page 375: ......