604
CompoNet Explicit Messages
Appendix A
Function
Setting
Write/
Read
Sets each function.
Bit status:
ON: Enabled,
OFF: Disabled
Moving average: 0;
Scaling: 1;
Peak/bottom hold: 2;
Top/valley hold: 3;
Comparator: 4;
Cumulative counter: 5;
Rate of change: 6
Write:
10 hex
Read:
0E hex
0A hex
01 to 04
hex
6E hex
1 byte
1 byte
Scaling
Type Set-
ting
Write/
Read
Default scaling: 0:
User scaling: 1
Write:
10 hex
Read:
0E hex
0A hex
01 to 04
hex
6F hex
1 byte
1 byte
Scaling
Point 1 Set-
ting
Write/
Read
Sets an analog value as
the 0% value for user
scaling.
Write:
10 hex
Read:
0E hex
0A hex
01 to 04
hex
70 hex
2 bytes
(
−
28000 to
28000)
2 bytes
(
−
28000 to
28000)
Scaling
Point 2 Set-
ting
Write/
Read
Sets an analog value as
the 100% value for user
scaling.
Write:
10 hex
Read:
0E hex
0A hex
01 to 04
hex
71 hex
2 bytes
(
−
28000 to
28000)
2 bytes
(
−
28000 to
28000)
Offset
Compensa-
tion after
Scaling
Write/
Read
Compensates for scal-
ing errors with an offset
value.
Write:
10 hex
Read:
0E hex
0A hex
01 to 04
hex
72 hex
2 bytes
(
−
28000 to
28000)
2 bytes
(
−
28000 to
28000)
Maximum
Value Read
Read/
Reset
Reads the maximum
value after power is
turned ON.
Read:
0E hex
Reset:
35 hex
0A hex
01 to 04
hex
73 hex
---
2 bytes
Minimum
Value Read
Read/
Reset
Reads the minimum
value after power is
turned ON.
Read:
0E hex
Reset:
35 hex
0A hex
01 to 04
hex
74 hex
---
2 bytes
Peak Value
Read
Read The peak value is held
while the hold function
is enabled. The held
value is read by this
message.
0E hex
0A hex
01 to 04
hex
75 hex
---
2 bytes
Bottom
Value Read
Read The bottom value is held
while the hold function
is enabled. The held
value is read by this
message.
0E hex
0A hex
01 to 04
hex
76 hex
---
2 bytes
Top Value
Read
Read The top value is held
while the hold function
is enabled. The held
value is read by this
message.
0E hex
0A hex
01 to 04
hex
77 hex
---
2 bytes
Top Detec-
tion Timing
Flag Read
Read Reads the timing for
detecting top values.
0E hex
0A hex
01 to 04
hex
78 hex
---
1 byte
Valley
Value Read
Read The valley value is held
and read.
0E hex
0A hex
01 to 04
hex
79 hex
---
2 bytes
Explicit
message
Read
/write
Function Command
Response
Service
code
Class
ID
Instance
ID
Command data
Service data
Attribute
ID
Data
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...