548
Temperature Input Unit Functions
Section 11-6
Timing for Setting Data
Setting the Hysteresis Using CX-Integrator
1,2,3...
1.
Click the
Top/Valley
Tab and input the hysteresis in the
Hysteresis
Field.
2.
Return to the
General
Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button to reset the Unit.
3.
Click the
OK
Button and exit the window.
Note
The hysteresis set for the top/valley hold function is also used by the compar-
ator function.
Setting the One-shot Time
1,2,3...
1.
Select the
Top/Valley
Tab Page and input the desired value in the
Shot Off
Delay
Field.
Temperature
input value
Set hysteresis value
×
2
Top/Valley Detection
Timing Flag
Delay
Valley hold value
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...