331
Units with Screw Terminal Blocks
Section 6-6
Switch Settings
Setting the Node Address
The node address is set as a decimal number with the 10s digit set on the left
rotary switch and the 1s digit set on the right rotary switch. (The maximum
node address is 63.)
The setting on the rotary switches is read when power is turned ON.
Setting the Input Ranges
Note
(1) Always use the default setting (OFF) for pin 7.
(2) Always set pin 8 to ON if the DIP switch is used to set the ranges. If this
pin is OFF, the DIP switch settings will not be enabled.
(3) The DIP switch settings are read when the power is turned ON.
■
Input CH0/CH1 range (common)
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1s digit of node address
10s digit of node address
Pin No.
Setting
Specification
1
Input CH0/CH1 range settings
(common)
Default setting: All pins OFF
See the next table
2
3
4
Input CH2/CH3 range settings
(common)
Default setting: All pins OFF
See the next table
5
6
7
Always OFF.
Always set this pin to OFF. Malfunctions
may occur if it is set to ON.
8
Range setting method
OFF: Use CX-Integrator.
ON: Use DIP switch.
1
2
3
4
5
6
7
8
ON
Input range
Pin 1
Pin 2
Pin 3
0 to 5 V
OFF
OFF
OFF
1 to 5 V
ON
OFF
OFF
0 to 10 V
OFF
ON
OFF
–10 to 10 V
ON
ON
OFF
4 to 20 mA
OFF
OFF
ON
0 to 20 mA
ON
OFF
ON
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...