87
Power Supply Wiring
Section 3-5
An OMRON S82-series Power Supply for the communications power supply
for CompoNet Slave Units is recommended.
Note
(1) For network power supply Slave Units, the external I/O power supply is
also provided through the Flat Cable from the communications power
supply connected to the Master Unit or the Repeater Unit.
When calculating the output current of the communications power supply,
always include the external I/O current consumption and actual load cur-
rent for network power supply Slave Units.
For example, the power supply current consumption for Bit Slave Unit is
expressed by the following formula.
• Input Bit Slave Units:
Communications power supply current consumption = Bit Slave Unit com-
munications current consu (Bit Slave Unit input current
×
number
of inputs used) + (sensor current consumption
×
number of sensors used)
• Output Bit Slave Units:
Communications power supply current consumption = Bit Slave Unit com-
munications current consu (actual load current
×
number of actu-
ators used)
• I/O Bit Slave Units:
Communications power supply current consumption = Bit Slave Unit com-
munications current consu (Bit Slave Unit input current
×
number
of inputs used) + (sensor current consumption
×
number of sensors used)
+ (actual load current
×
number of actuators used)
(2) Use a power supply with sufficient capacity considering the inrush current
at startup.
For details on current consumption for each Unit, refer to
Appendix C Current
Consumption Summary
.
3-5-2
Connection Locations for Communications Power Supplies
Round Cable I
A 24-VDC power supply is connected individually to each Slave Unit. Power
does not need to be supplied to the Master Unit.
Output current
Use a power supply that equals or exceeds the following total
current consumption:
• The current consumption of all Word Slave Units and
Repeater Units
• The current consumption of all Bit Slave Units and the current
consumption of their external I/O
Insulation
Between output and AC power and between output and chas-
sis ground
Item
Specification
+ −
Master Unit
Open Type Connector
Round cable I
Communications
connector
24-VDC com-
munications
power supply
Supply communications power directly to each Slave Unit.
Word Slave Unit
Terminating Resistor
Open Type Connector
Open Type Connector
Open Type Connector
Word Slave Unit
Word Slave Unit
Overcurrent
protection (See note.)
(current limit: 4 A)
Note:
When using the UL standards, please install a unit
to restrict current between the external power
supply and this unit to 4 A. (Only communications
power supply)
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...