372
Overview of Temperature Input Units
Section 7-2
■
Allocating Selected I/O Data Patterns
Data such as Status Flags can be allocated together with Temperature Data 1
as I/O in the following combinations. The data to be combined can be selected
from the CX-Integrator.
Example: Allocating Temperature Data 1 + Top/Valley Detection Timing Flags
in the Master Unit using normal display.
■
Using the CX-Integrator
1,2,3...
1.
Turn ON the power supply to the Temperature Input Unit.
2.
Double-click the icon of the Temperature Input Unit to be set in the Network
Configuration Window or right-click the icon and select
Parameter - Edit
.
The Configuration Window will be displayed.
3.
Click the
General
Tab and select an I/O data pattern in the
Default Con-
nection Path (In)
Field. The following example shows selecting the temper-
ature data and status flags.
4.
Click the
Transfer [PC to Unit]
Button to download the data and then click
the
Reset
Button to reset the Unit.
5.
Click the
OK
Button and exit the window.
I/O Data
Temperature Data 1
Temperature Data 1 is used to monitor the temperature input value. The tem-
perature input value is allocated as the default setting, but any of the following
data can be allocated: temperature input value, peak value, bottom value, top
value, valley value, or rate of change.
Note
The comparator function can be used for the data allocated as Temperature
Data 1.
15
8
7
0
First word + 0CH
Temperature Data 1 for Input CH0
First word + 1CH
Temperature Data 1 for Input CH1
First word + 2CH
Temperature Data 1 for Input CH2
First word + 3CH
Temperature Data 1 for Input CH3
First word + 4CH
Top Detection Timing Flag
Valley Detection Timing Flag
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...