432
Clamp Terminal Blocks
Section 9-4
9-4
Clamp Terminal Blocks
9-4-1
Two-point Input/Two-point Output Units (IP54)
CRT1B-MD04SLP/CRT1B-MD04SLP-1
Input Section Specifications
Note
The current consumption is for Bit Slave Unit communications cur-
rent when all inputs and outputs are OFF, i.e., it does not include
input device current consumption or output load current consump-
tion. The communications power supply is also used for the I/O
power supply for sensors and actuators. Be sure to consider the
sensor and actuator current consumption and the number of sen-
sors and actuators connected. The power supply current consump-
tion is expressed by the following formula.
Communications power supply current consumption = Bit Slave
Unit communications current consu (Bit Slave Unit input
current
×
number of inputs used) + (sensor current consumption
×
number of sensors used) + (actual load current x number of actua-
tors used)
Item
Specification
Model
CRT1B-MD04SLP
CRT1B-MD04SLP-1
I/O capacity
2 inputs
Internal I/O common line
NPN
PNP
ON voltage
10.5 VDC min. (between each input
terminal and the V terminal)
10.5 VDC min. (between each input
terminal and the G terminal)
OFF voltage
5 VDC max. (between each input
terminal and the V terminal)
5 VDC max. (between each input
terminal and the G terminal)
OFF current
1 mA max.
Input current
3.0 mA min./input (at 10.5 VDC)
Sensor power supply voltage
Communications power supply voltage 0 V (max.)
Communications power supply voltage
−
1 V (min.)
ON delay
1.5 ms max.
OFF delay
1.5 ms max.
Number of circuits per common
2 inputs/common
Power short-circuit detection
Supported.
Isolation method
No isolation
Input indicators
LEDs (yellow)
Degree of protection
IEC standard IP54
Installation
Screw installation (M4)
Power supply type
Network power supply
Communications power supply
current consumption (See note.)
80 mA max. for 24-VDC power sup-
ply voltage
90 mA max. for 14-VDC power sup-
ply voltage
75 mA max. for 24-VDC power sup-
ply voltage
85 mA max. for 14-VDC power sup-
ply voltage
Input device supply current
80 mA/2 points
Weight
191 g max.
191 g max.
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...