4
Features of CompoNet Slave Units
Section 1-1
Expansion Using
Expansion Units
One Expansion Unit can be added to a Digital I/O Slave Unit (with 2-tier termi-
nal block and 16 points). This extends the range of possible system configura-
tions by making it possible to expand to a variety of I/O combinations, e.g., 16
inputs and 8 outputs or 24 inputs (16 8 inputs).
Scaling
Converted data can be scaled to any value by the user. Ladder program cal-
culations for the Master Unit are not required if the scaling function is used
with the Slave Unit. The offset compensation function can also be used to off-
set scaled values.
These settings are made by using the CX-Integrator.
Last Maintenance Date
(Maintenance Function)
The date that maintenance was performed can be written in the Slave Unit by
using the CX-Integrator.
Cumulated Count
The cumulated count function calculates the integral time for input (or output)
analog values and reads the cumulated value. Monitor values can be set in
Units. If the cumulated counter value exceeds the set monitor value, the
Cumulated Counter Over Flag in general status turns ON.
These values can be set and read by using the CX-Integrator.
Moving Average
An Analog Input Unit or Temperature Input Unit can calculate the moving aver-
age of the last eight inputs and use it as the converted data. Smooth input val-
ues can be obtained by averaging the inputs if there are rapid fluctuations in
the input.
Settings for averaging are made by using the CX-Integrator.
Setting the Number of AD
Conversion Points
The conversion cycle is 4 ms max. when using all 4 analog inputs. The AD
conversion cycle can be made faster if fewer AD conversion points are used.
Rate of Change
Calculations
You can find the rate of change during the set data sampling cycle for the
input value to an Analog Input Unit or Temperature Input Unit.
The rate of change settings are made by using the CX-Integrator.
Comparator
Input data captured into the Analog Input Slave Unit/Temperature Input Unit or
calculation data is compared to alarm settings (Alarm Trip Point High (HH),
Warning Trip Point High (H), Warning Trip Point Low (L), and Alarm Trip Point
Low (LL)) and the results can be reflected in the "Analog Status Flag" (or
"Temperature Data Status Flag"). The Normal Flag (pass signal) turns ON for
values that are in set range.
The alarm settings are made by using the CX-Integrator.
Peak/Bottom Hold
The peak/bottom hold function holds the maximum (peak) or the minimum
(bottom) input value to an Analog Input Unit or Temperature Input Unit. The
maximum (peak) or minimum (bottom) value can be compared with an alarm
set value and used to turn ON an alarm flag as status data. This is called the
comparator function.
The peak/bottom hold settings are made by using the CX-Integrator.
Top/Valley Hold
The top/valley hold function holds the top or valley input value to an Analog
Input Unit or Temperature Input Unit. The Top/Valley Detection Timing Flag
can be used to check when top and valley values were detected. The top and
valley values can be compared with an alarm set value and used as status
data to turn ON alarm flags (comparator function).
The top/valley hold settings are made by using the CX-Integrator.
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...