111
Connecting External I/O for Slave Units
Section 3-6
Note
When using a DCN4-MD4 Multidrop Connector to branch a Communications
Cable, bind together the loose wires where the cable comes out of the Hood
Cover. Wire the Communications Cable and loose-wire cable so that they do
not interfere with each other.
3-6-4
Connecting to Screw-less Clamp Terminal Blocks
For Slave Units with screw-less clamp terminal blocks, the terminal blocks can
be easily wired by inserting pin terminals. Follow the procedure below to con-
nect the external device cable to a screw-less clamp terminal block.
■
Applicable Pin Terminals
When wiring an external device cable to a screw-less clamp terminal block,
special pin terminals must be placed on the cable wires. The applicable pin
terminals are listed in the following table.
The pin terminal conductor should be about 8 to 10 mm in length.
■
Wiring to the Screw-less Clamp Terminal Block
Inserting Pin Terminals
Insert the pin terminal all the way to the back of the terminal hole.
Removing Pin Terminals
Press down the release button next to the terminal hole with a small flat-blade
screwdriver and pull out the pin terminal while the release button is down.
The following screwdriver is recommended for removing pin terminals.
Name
Applicable wire size
Crimp tool
Manufacturer
H0.5/14 orange
0.5 mm
2
/AWG20
PZ6 roto
Weidmuller Co. Ltd.
H0.75/14 white
0.75 mm
2
/AWG18
H1.5/14 red
1.5 mm
2
/AWG16
Conductor length: 8 to 10 mm
Model
Manufacturer
SD0.6
×
3.5
×
100 Flat-blade
Screwdriver
Weidmuller Co. Ltd.
Insert the pin terminal all the way to the back.
Small flat-blade screwdriver
Release button
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...