CompoNet Explicit Messages
Appendix A
Setting and Monitoring the Outputs
Explicit
message
Read
/write
Function Command
Response
Service
code
Class
ID
Instance
ID
Command data
Service data
Attribute
ID
Data
Terminal
Mainte-
nance Infor-
mation
Monitor
Mode
Read Reads the monitor mode
for maintenance infor-
mation of the output (No.
1 to 32) specified by the
Instance ID.
0E hex
09 hex
01 to 20
hex
65 hex
---
1 byte
00 hex: Total
ON time
mode
01 hex: Con-
tact opera-
tion counter
mode
Write Writes the monitor mode
for maintenance infor-
mation of the output (No.
1 to 32) specified by the
Instance ID.
10 hex
09 hex
01 to 20
hex
65 hex
1 byte
00 hex: Total
ON time mode
01 hex: Contact
operation
counter mode
---
Set Value
for Output
Total ON
Time or
Contact
Operation
Counter
Read Reads the set value for
the total ON time (unit: s)
or number of contact
operations (unit: opera-
tion) for the output (No. 1
to 32) specified by the
Instance ID.
0E hex
09 hex
01 to 20
hex
68 hex
---
4 bytes
00000000 to
FFFFFFFF
hex
(0 to
4294967295)
Write Writes the set value for
the total ON time (unit: s)
or number of contact
operations (unit: opera-
tion) for the output (No. 1
to 32) specified by the
Instance ID.
10 hex
09 hex
01 to 20
hex
68 hex
4 bytes
00000000 to
FFFFFFFF hex
(0 to
4294967295)
---
Output
Total ON
Time or
Contact
Operation
Counter
Read
Read Reads the total ON time
(unit: s) or number of
contact operations (unit:
operation) for the output
(No. 1 to 32) specified by
the Instance ID.
0E hex
09 hex
01 to 20
hex
66 hex
---
4 bytes
00000000 to
FFFFFFFF
hex
(0 to
4294967295)
Reset for
Output
Total ON
Time or
Contact
Operation
Counter
Reset
Reset Resets the total ON time
(unit: s) or number of
contact operations (unit:
operation) for the output
(No. 1 to 32) specified by
the Instance ID to 0.
05 hex
09 hex
01 to 20
hex
66 hex
---
---
Monitor
Status for
Output
Total ON
Time or
Contact
Operation
Counter
Read
Read Reads the monitor sta-
tus for total ON time or
contact operation
counter for the output
(No. 1 to 32) specified by
the Instance ID.
0E hex
09 hex
01 to 20
hex
67 hex
---
1 byte
00 hex:
Within range
01 hex: Out
of range
(over the
monitor
value)
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...