560
Temperature Input Unit Functions
Section 11-6
6.
Click the
OK
Button. The Edit Calculation Data Window will close.
7.
Return to the
General
Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button to reset the Unit.
8.
Click the
OK
Button and exit the window.
11-6-10 Input Error Detection Disable Function
Description
If there are inputs that are not being used, input error detection (including off-
wire detection) can be disabled. If this function is used, the Temperature Input
Warning Flag and Off-wire Detection Flags will be OFF regardless of the con-
nection status of the input sensor or temperature range.
When this function is enabled, the temperature data is set to 7FFF hex (7FFF
FFFFF when 1/100 Display Mode is being used).
1,2,3...
1.
Turn ON the power supply to the Temperature Input Unit.
2.
Double-click the icon of the Temperature Input Unit to be set in the Network
Configuration Window or right-click the icon and select
Parameter - Edit
.
The Configuration Window will be displayed.
3.
Click the tab for the input where the input error detection disable function
is to be set, and select the
Disable Input Error’s Detection
Check Box in the
Function Choice
Area.
4.
Return to the
General
Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button to reset the Unit.
5.
Click the
OK
Button and exit the window.
Note
Use this function only if there are unused inputs. If this function is used while a
sensor is connected, it will not detect input errors (including disconnections).
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...