568
Temperature Input Unit Functions
Section 11-6
Input Terminal Connections
Wiring for Adjusting the Upper and Lower Limits
Lead wires for adjusting bias
Checking the Wiring and
Making Adjustments
Adjusting the Upper and Lower Limit Values
1,2,3...
1.
Set the wiring for adjusting the upper and lower limits. If connecting the
precision digital multimeter (DMM), use a ferrule for two wires.
2.
Check the sensor and input type being used.
Note
When using an R, S, B, E, or W sensor, use a compensating conductor for a K
thermocouple. In addition, when using an R, S, or B sensor, set the input type
to K (0.0 to 500.0
°
C). When using an E or W sensor, set the input type to K
(
−
200 to 1,300
°
C).
3.
Connect the CX-Integrator to the CompoNet network and go online.
4.
Upload settings to the CX-Integrator.
5.
Turn ON the power supplies of all Units, including the Temperature Input
Unit to be adjusted. Wait approximately 30 minutes for the Temperature In-
put Unit's internal temperature to stabilize.
6.
Double-click the icon of the Temperature Input Unit to be set in the Network
Configuration Window or right-click the icon and select
Parameters - Edit
.
The Configuration Window will be displayed.
7.
Click the tab for the input that will be adjusted and click the
Adjustment
Button.
NC
NC
NC
NC
NC
NC
NC
NC
0
−
1
−
2
−
3
−
1
+
0
+
2
+
3
+
Ferrule for two wires
Cold junction compensator
DMM
STV
NC
NC
NC
NC
NC
NC
NC
NC
0
−
1
−
2
−
3
−
1
+
0
+
2
+
3
+
INPUT
OUTPUT
Cold junction compensator
Compensating conductors
ZERO-CON (0
°
C bath)
Short-circuit
0
°
C/32
°
F
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...