542
Temperature Input Unit Functions
Section 11-6
To scale the temperature input values to the scale required by the user, use
the CX-Integrator to set the conversion values (
−
28,000 to 28,000) for two
points in the scale (the 100% value and 0% value).
Note
1.
The default values are 0 and 28,000.
2.
Reverse scaling, where the 0% scaling value is higher than the 100% scal-
ing value, is also supported.
Offset Compensation
The scaling function is equipped with offset compensation, which can com-
pensate for any error that occurs during scaling. The offset amount is added
to the scaled line as shown in the following diagram. The offset value can be
input between
−
28,000 to 28,000. Make sure that underflow or overflow does
not occur. The High Limit is 7FFE hex and the Low Limit is 8000 hex. (The
High Limit is 7FFFFFFE Hex and the Low Limit is 80000000 Hex for 1/100
Display Mode.)
Note
The offset value can be set even when using default scaling.
Setting Using CX-Integrator
1,2,3...
1.
Turn ON the power supply to the Temperature Input Unit.
2.
Double-click the icon of the Temperature Input Unit to be set in the Network
Configuration Window or right-click the icon and select
Parameter - Edit
.
The Configuration Window will be displayed.
3.
Click the tab for the input where scaling is to be performed, and select the
Scaling
Check Box in the
Function Choice
Area.
0%
100%
Scaling value
Value for 100% set by user
(Scaling point 2)
Conversion
Value for 0% set by user
(Scaling point 1)
Input signal range
Upper limit: 7FFE hex (32766)
100% scaling value
Scaled line
0% scaling
Offset value
(–28,000 to 28,000)
Input signal range
0%
100%
Lower limit: 8000 hex (
−
32768)
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...