321
Summary of the Analog Output Slave Units
Section 6-3
■
Output Range: 0 to 20 mA
Data of 0000 to 1770 Hex (0 to 6000) is converted to current from 0 to 20 mA
and output. The output data range for which conversion is possible is from
0000 to 189C Hex (0 to 6300) and for this case the output data becomes from
0 to 21 mA.
Output Range
Settings
Setting of output range is performed using Analog Output Slave Unit DIP
switches, CX-Integrator, or Explicit message.
The method for setting the output range using CX-Integrator is described
below.
Please see "
11-1 CX-Integrator
" on page 481 regarding details for CX-Inte-
grator.
1,2,3...
1.
Turn ON the power to the CompoNet Slave Unit.
2.
Double-click the icon of the Analog Output Unit to set in the Network Con-
figuration Window to open the Configuration Window. (Alternatively, right-
click the icon and select
Parameters - Edit
from the pop-up menu.)
3.
Select the tab for the channel for which you would like to change the range
and select any output range from the pull-down list of "Output Range".
4.
Return to the General Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button to reset the Unit.
5.
Click the
OK
Button and exit the window.
189C
(6300)
1770
(6000)
0000 (0)
0 mA
21 mA
20 mA
FFFF
7FFF
Conversion data
Hexadecimal (decimal)
Current
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...