Temperature Input Unit Functions
Section 11-6
7.
Return to the
General
Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button to reset the Unit.
8.
Click the
OK
Button and exit the window.
11-6-8 Temperature Range Count
Description
This function times (in 1-second units) how long the temperature input value is
within a user-set temperature range. The range count (zone count) can indi-
cate when preventative maintenance is required for devices or applications
that deteriorate at a fixed rate within the user-set temperature range.
Select the temperature range settings on the
Comparator
Tab Page. The
temperature range boundaries are defined by the High High Limit (HH), High
Limit (H), Low Low Limit (LL), or Low Limit (L). If the time within the set tem-
perature range exceeds the monitor value, it indicates that a threshold value
has been exceeded. The status can be read in the Monitor Window or via an
explicit message to know when a threshold has been exceeded.
The Over Threshold status can be read in the Maintenance Information Win-
dow or via an explicit message.
Setting Using CX-Integrator
1,2,3...
1.
Turn ON the power supply to the Temperature Input Unit.
85
°
C
10
°
C
Counting starts when this
temperature is exceeded.
When the temperature range is
set to 10
°
C above the set
temperature (95
°
C), the function
counts how long the temperature
is within that 10
°
C range.
Counting
starts
Temperature
Time
Counting
starts
Counting
stops
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...