Analog I/O Slave Unit (input) Functions
Section 11-4
User Scaling
Analog input values (count values) are scaled to user-defined values. The
conversion values for 100% and 0% are set using the CX-Integrator.
Note
Reverse scaling, where the 0% scaling value is higher than the 100% scaling
value, is also supported.
Offset Compensation
Scaling the analog input values of linear sensors to distances produces
mounting error in the sensor. Offset compensation compensates for the error
that occurs during scaling. The offset amount is added to the scaled line
before processing, as shown in the following diagram. The offset (error) value
can be input between
–
28,000 to 28,000, but make sure that underflow or
overflow does not occur. The High Limit is 7FFE hex and the Low Limit is
8000 hex.
Note
The offset value can be set even when using default scaling.
Setting Using the CX-Integrator
1,2,3...
1.
Turn ON the power supply to the CompoNet Slave Unit.
Input
range
0 to 5 V
0 to 10 V
1 to 5 V
−
10 to 10 V
(CRT1-
AD04 only)
0 to
20 mA
4 to
20 mA
100%
Set using CX-Integrator (–28,000 to 28,000)
0%
Set using CX-Integrator (–28,000 to 28,000)
Discon-
nected
line
0000 hex
0000 hex
7FFF hex
0000 hex
0000 hex
7FFF hex
0%
100%
Scaling value
Value for 100% set by user
(Scaling point 2)
Conversion
Value for 0% set by user
(Scaling point 1)
Input signal range
Upper limit: 7FFE hex (32766)
100% scaling value
Scaled line
0% scaling
Offset value
(–28,000 to 28,000)
Input signal range
0%
100%
Lower limit: 8000 hex (
−
32768)
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...