385
Temperature Input Units
Section 7-5
Setting the Input Type
Setting with the DIP
Switch
The input type can be set using the DIP switch or the CX-Integrator.
Set each pin according to the following table.
CRT1-TS04T
Note
If the settings are incorrect, the MS Indicator will flash red and the
Unit will not operate. In this case, make the settings again and reset
the power supply.
Pin No.
Setting
Specifications
SW1
Sets the input type (input
range)
Refer to the following table.
Default setting: All pins OFF
SW2
SW3
SW4
SW5
Always OFF
Always set this pin to OFF. Malfunctions may
occur if it is set to ON.
SW6
Selects °C or °F display.
OFF: °C conversion
ON: °F conversion
Default setting: OFF
SW7
Always OFF
Always set this pin to OFF. Malfunctions may
occur if it is set to ON.
SW8
Selects the input type set-
ting method.
OFF: Set with CX-Integrator.
ON: Set with DIP switch.
Note
When the input type is set with the DIP
switch, all inputs are set to the same
input type. To set different input types,
use the CX-Integrator to make the set-
tings.
SW1
SW2
SW3
SW4
Input type
OFF
OFF
OFF
OFF
R
ON
OFF
OFF
OFF
S
OFF
ON
OFF
OFF
K (
−
200 to 1300
°
C)
ON
ON
OFF
OFF
K (0.0 to 500.0
°
C)
OFF
OFF
ON
OFF
J (
−
100 to 850
°
C)
ON
OFF
ON
OFF
J (0.0 to 400.0
°
C)
OFF
ON
ON
OFF
T
ON
ON
ON
OFF
E
OFF
OFF
OFF
ON
L (
−
100 to 850
°
C)
ON
OFF
OFF
ON
L (0.0 to 400.0
°
C)
OFF
ON
OFF
ON
U
ON
ON
OFF
ON
N
OFF
OFF
ON
ON
W
ON
OFF
ON
ON
B
OFF
ON
ON
ON
PL2
ON
ON
ON
ON
Not used.
1
2
3
4
5
6
7
8
ON
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...