41
Communications Cable
Section 2-3
Baud Rate of
1.5 Mbps
Note
(1) The number of Units per branch is the maximum number of Slave Units
or Repeater Units that can be connected to one branch using multidrop
or T-branch connections (sub-branch lines).
(2) Lines cannot be branched from the trunk line. (Only multidrop connec-
tions are possible from the trunk line or sub-trunk lines.)
(3) Sub-branch lines can be branched from branch lines.
Baud Rate of
93.75 kbps
Note
The number of Units per branch is the maximum number of Slave Units or
Repeater Units that can be connected to one branch using multidrop or T-
branch connections (sub-branch lines).
Item
Round cable I
Round cable II
Flat Cable I/II
Without
branch-
ing
With
branch-
ing
Length per trunk line or sub-trunk line
100 m
(300m)
30 m
(90m)
30 m (90 m)
Branch line length
Not sup-
ported.
(See
note 2.)
2.5 m
2.5 m
Total branch line length
Not sup-
ported.
(See
note 2.)
25 m
25 m
Restrictions on branch line locations
---
3/m
3/m
Number of Units per branch (See note 1.)
3
3
Maximum sub-branch line length
Not sup-
ported.
0.1 m (See note 3.)
Total sub-branch line length
Not sup-
ported.
2 m (See note 3.)
Number of Slave Units (including Repeater
Units)
32
32
32
Item
Round cable I
Round cable II
Flat Cable I/II
Length per trunk line or sub-trunk line
500 m
Unrestricted wiring
is enabled for a total
length of 200 m.
Branch line length
6 m
Total branch line length
120 m
Restrictions on branch line locations
3/m
Number of Units per branch (See note.)
1
Maximum sub-branch line length
---
Total sub-branch line length
---
Number of Slave Units (including Repeater
Units)
32
32
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...