530
Analog I/O Slave Unit (output) Functions
Section 11-5
4.
Return to the General Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button to reset the Unit.
5.
Click the
OK
Button and exit the window.
11-5 Analog I/O Slave Unit (output) Functions
11-5-1 Scaling
Description
In default setting, the output values are scaled to a count between 0 to 6,000
and converted to analog values in the output signal range. The scaling func-
tion allows user-specified scaling (or industry-specific units) for output signal
ranges. The function eliminates the need for ladder programming in the Mas-
ter Unit to perform math operations. The following two methods of scaling can
be used.
Default Scaling
Default scaling converts analog output values into voltage or current values.
The units used are mV or
µ
A. When default scaling is selected, scaling is per-
formed according to the output range, as shown in the following table.
Output
range
0 to 5 V
0 to 10 V
1 to 5 V
–10 to 10 V
0 to
20 mA
4 to
20 mA
100%
5,000 mV
10,000
mV
5,000 mV
10,000 mV
20,000
µ
A 20,000
µ
A
0%
0000 mV
0000 mV
1,000 mV
–10,000 mV 0000
µ
A
4,000
µ
A
Discon-
nected
line
---
---
7FFF hex
---
---
7FFF hex
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...