397
Expansion Unit Specifications
Section 8-2
8-2-2
Eight-point Output Units
XWT-OD08/XWT-OD08-1
Output Section Specifications
Component Names and Functions (Same for XWT-OD08 and XWT-OD08-1)
Operation Indicators
The meanings of the output indicators are given in the following table.
Item
Specification
Model
XWT-OD08
XWT-OD08-1
Internal I/O common
NPN
PNP
I/O capacity
8 outputs
Rated output current
0.5 A/output, 2.0 A/common
Residual voltage
1.2 V max.(0.5 A DC, between each
output terminal and the G terminal)
1.2 V max.(0.5 A DC, between each
output terminal and the V terminal)
Leakage current
0.1 mA max.
0.1 mA max.
ON delay
0.5 ms max.
OFF delay
1.5 ms max.
Number of circuits per
common
8 outputs/common
XWT-OD08
REMOTE TERMINAL
0UT
0
7
6
5
4
3
2
1
Removable terminal block
Indicator Section
Shows the status of each output.
Name
LED status
I/O status
Meaning
0 to 7
Lit yellow.
Output ON
The output is ON.
Not lit.
Output OFF
The output is OFF.
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...