587
Troubleshooting
Section 12-2
Analog I/O Slave
Units (Inputs)
The disconnection display
does not clear.
• The Sensor is disconnected.
• Restore the Sensor connec-
tion.
• Check the connected Sensor
and input type again.
No disconnection display.
• Disconnection is not dis-
played for ranges other than 1
to 5 V and 4 to 20 mA.
---
The conversion cycle is too
long.
• The setting of the number of
AD conversion points is on
the maximum (4 points).
• The processing time gets
longer each time a function is
added.
• Reduce the number of points
if some inputs are unneces-
sary, and execute conversion
again.
• Delete any unused functions,
and execute conversion
again.
Analog I/O Slave
Units (Outputs)
The expected value is not held
when communications errors
occur.
• The output value that is set
for communications errors is
incorrect.
• Check the output setting for
communications errors.
Temperature Input
Units
The 1/100 Display Mode has
been set, but the display reads
0.
The allocated word is the one
word in the normal display
area.
Either change the default con-
nection path to the 1/100 dis-
play area or select a
connection path in the Master
Unit for the 1/100 display area.
The temperature range
counter is not counting even
though the temperature value
is set as the count condition.
The comparator function is not
effective.
Enable the comparator. (The
power must be turned OFF
and then ON again.)
The Top/Valley Count Over
Flag will not go ON.
• The top/valley hold function is
not enabled.
• Enable the top/valley hold
function. (The power must be
turned OFF and then ON
again.)
• The hysteresis setting is too
high.
• The hysteresis setting is 0.
• Adjust the hysteresis setting.
The comparator does not oper-
ate as expected even though
the function and hysteresis
value have been set.
• The temperature display set-
ting has been switched (
°
C to
°
F or vice versa).
Check the decimal point posi-
tion and
°
C/
°
F display for the
input type and display mode.
If these settings have been
changed during operation,
check the comparator and hys-
teresis settings and correct if
necessary.
• The decimal point position
was read incorrectly.
Model
Problem
Cause
Possible correction
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...