509
Analog I/O Slave Unit (input) Functions
Section 11-4
4.
Return to the General Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button to reset the Unit.
5.
Click the
OK
Button and exit the window.
11-4-3 Scaling
Description
The default setting is used to perform AD conversion of analog input values,
scaling them to a count between 0 and 6,000. Scaling can be used to change
scaled values that correspond to the input signal range into other values
required by the user (industry unit values). Scaling also eliminates the need
for ladder programming in the Master Unit to perform math operations. The
following two methods of input scaling can be used.
Default Scaling
Analog input values (count values) are converted to the original voltage and
current values. The units used are mV or
µ
A. When default scaling is
selected, scaling is performed according to the range used, as shown in the
following table.
Input
range
0 to 5 V
0 to 10 V
1 to 5 V
−
10 to 10 V
(CRT1-
AD04 only)
0 to
20 mA
4 to
20 mA
100%
5,000 mV
10,000
mV
5,000 mV
10,000 mV
20,000
µ
A 20,000
µ
A
0%
0000 mV
0000 mV
1,000 mV
–10,000 mV 0000
µ
A
4,000
µ
A
Discon-
nected
line
0000 hex
0000 hex
7FFF hex
0000 hex
0000 hex
7FFF hex
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...