317
Summary of the Analog Input Slave Units
Section 6-2
The meaning for each bit is as described below.
Analog Data 1 + Top/Valley
Detection Timing Flags
This data pattern consists of Analog Data 1 followed by the Top/Valley Detec-
tion Timing Flags and is allocated in the Master Unit using the following data
format (5 words (10 bytes)).
15
8
7
0
+1
+0
+3
+2
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
+0
BW0
T_ST0 V_ST0
HH0
H0
PS0
L0
LL0
Input
CH0
Lower
byte
+1
BW1
T_ST1 V_ST1
HH1
H1
PS1
L1
LL1
Input
CH1
Upper
byte
+2
BW2
T_ST2 V_ST2
HH2
H2
PS2
L2
LL2
Input
CH2
Lower
byte
+3
BW3
T_ST3 V_ST3
HH3
H3
PS3
L3
LL3
Input
CH3
Upper
byte
Bit
Abbrevi-
ation
Name
Details
0
LLx
Compara-
tor Result
Flag
Low Low Limit
Alarm Flag
Turns ON when the value of data
allocated in Analog Data 1 drops
below the Low Low Limit alarm set-
ting.
1
Lx
Low Limit Alarm
Flag
Turns ON when the value of data
allocated in Analog Data 1 drops
below the Low Limit alarm setting.
2
PSx
Normal Flag
(pass signal)
Turns ON when none of the alarms
(High High Limit, High Limit, Low
Low Limit, and Low Limit) have been
output.
3
Hx
High Limit
Alarm Flag
Turns ON when the value of data
allocated in Analog Data 1 exceeds
the High Limit alarm setting.
4
HHx
High High Limit
Alarm Flag
Turns ON when the value of data
allocated in Analog Data 1 exceeds
the High High Limit alarm setting.
5
V_STx
Top/Val-
ley Detec-
tion
Timing
Flags
Valley Detec-
tion Timing Flag
Turns ON at the timing when a valley
is detected by the top/valley hold
function and becomes 0 (OFF) after
passing of one-shot time.
6
T_STx
Top Detection
Timing Flag
Turns ON at the timing when a top is
detected by the top/valley hold func-
tion and becomes 0 (OFF) after
passing of one-shot time.
7
BWx
Disconnected Line Detec-
tion Flag
Turns ON when a disconnection is
detected.
15
8
7
0
+1
+0
+3
+2
+5
+4
+7
+6
+9
+8
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...