594
CompoNet Explicit Messages
Appendix A
Explicit Messages Common to Slave Units
Refer to
1-1-3 CompoNet Slave Unit Functions
for information on which functions are supported by the various
Slave Units.
Setting and Monitoring the Unit Conduction Time
Reading Warning Status and Alarm Status
Note
For information on individual bits in the status areas of a Slave Unit, refer to the
Status Areas
section for
the Slave Unit.
Explicit
message
Read/
write
Function Command
Response
Service
code
Class ID
Instance
ID
Command data
Service data
Attribute
ID
Data
Unit Main-
tenance Set
Value
Read
Reads the set value
for Unit Conduction
Time (unit: 0.1 hr)
0E hex
95 hex
01 hex
73 hex
---
4 bytes
00000000 to
FFFFFFFF hex
(0 to 4294967295)
Write
Writes the set value
for Unit Conduction
Time (unit: 0.1 hr)
10 hex
95 hex
01 hex
73 hex
4 bytes
0000000
0 to
FFFFFFF
F hex
(0 to
4294967
295)
---
Unit Main-
tenance
Present
Value
Read
Reads the present
value for Unit Con-
duction Time (unit:
0.1 hr)
0E hex
95 hex
01 hex
71 hex
---
4 bytes
00000000 to
FFFFFFFF hex
(0 to 4294967295)
Unit Main-
tenance
Flag
Read
Reads the monitor
status of Unit Con-
duction Time
0E hex
95 hex
01 hex
72 hex
---
1 byte
00 hex: Within
range
01 hex: Out of
range (over the
monitor value)
Explicit
message
Read/
write
Function Command
Response
Service
code
Class ID
Instance
ID
Command data
Service data
Attribute
ID
Data
Warning
Status
Read
Read
Reads the Slave
Unit’s warning sta-
tus area.
0E hex
95 hex
01 hex
C5 hex
---
2 bytes
Alarm Sta-
tus Read
Read
Reads the Slave
Unit’s alarm status
area.
0E hex
95 hex
01 hex
C6 hex
---
2 bytes
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...