Temperature Input Unit Functions
Section 11-6
8.
Adjust the lower limit value. Input 18
Ω
from the six-dial resistance box to
the Temperature Input Unit's input terminals. Wait at least 1 minute for the
input to stabilize.
9.
Click the
Fix Lower Adjusting Value
Button in the Adjustment Window to
write the adjustment value.
10. Adjust the upper limit value. Input the resistance from the six-dial resis-
tance box. Refer to the following table for the appropriate resistance to in-
put. Wait at least 1 minute for the input to stabilize.
11. Click the
Fix Upper Adjusting Value
Button to write the adjustment value.
Type
Input resistance for upper
limit adjustment
PT100 (
−
200 to 850
°
C)
390
Ω
PT100 (
−
200 to 200
°
C)
180
Ω
Summary of Contents for CRT1 - 10-2009
Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Page 2: ......
Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ...x...
Page 16: ...xvi...
Page 24: ...xxiv Conformance to EC Directives 6...
Page 386: ...362 Units with Connectors Section 6 7...
Page 414: ...390 Temperature Input Units Section 7 5...
Page 430: ...406 Expansion Unit Specifications Section 8 2...
Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 502: ...478 Repeater Unit Section 10 2...
Page 508: ...484 CX Integrator Section 11 1...
Page 509: ...485 CX Integrator Section 11 1...
Page 602: ...578 Temperature Input Unit Functions Section 11 6...
Page 614: ...590 Device Maintenance Section 12 3...
Page 664: ...640 I O Power Supply Current Appendix E...
Page 672: ...648 Index...
Page 674: ...650 Revision History...