Chapter 5 List of Parameters GK600 User Manual
- 86 -
Parameter
Designation
Scope
Factory
default
Attr
C3-10 DO output center point
0: No center point
1: Center point is (C3-09)/2, and the
corresponding parameter value is
positive when FREQ is higher than
center point
2: Center point is (C3-09)/2, and the
corresponding parameter value is
positive when FREQ is lower than
center point
0
×
C3-11 DO output filtering time
0.00s~10.00s
0.00s
△
Group C4 Automatic Correction of Analog Input
C4-00 Analog correction
0: No correction
1:Correct AI1
2:Correct AI2
3:Correct EAI
0
×
C4-01
Sampling value of AI1
calibration point 1
Range: 0.00V~10.00V
1.00V
◎
C4-02
Input value of AI1
calibration point 1
Range: 0.00V~10.00V
1.00V
×
C4-03
Sampling value of AI1
calibration point 2
Range: 0.00V~10.00V
9.00V
◎
C4-04
Input value of AI1
calibration point 2
Range: 0.00V~10.00V
9.00V
×
C4-05
Sampling value of AI2
calibration point 1
Range: -10.00V~10.00V
1.00V
◎
C4-06
Input value of AI2
calibration point 1
Range: -10.00V~10.00V
1.00V
×
C4-07
Sampling value of AI2
calibration point 2
Range: -10.00V~10.00V
9.00V
◎
C4-08
Input value of AI2
calibration point 2
Range: -10.00V~10.00V
9.00V
×
C4-09
Sampling value of EAI
calibration point 1
Range: 0.00V~10.00V
1.00V
◎
C4-10
Input value of EAI
calibration point 1
Range: 0.00V~10.00V
1.00V
×
C4-11
Sampling value of EAI
calibration point 2
Range: 0.00V~10.00V
9.00V
◎
C4-12
Input value of EAI
calibration point 2
Range: 0.00V~10.00V
9.00V
×