Chapter 6 Specification of Parameters GK600 User Manual
- 122 -
b0-00
Frequency set mode
Range: 0~4
Factory default:
0
0: Master FREQ set
Output frequency of drive is determined by master frequency set source b0-01. Refer to
parameters b0-01 and b0-02 for further information.
1: Master & auxiliary computation result
Frequency set is the result of master & auxiliary computation. The master & auxiliary
computation relation is determined by b0-07. Master frequency is set by b0-01, while
auxiliary is set by b0-03.
2: Switch between master and auxiliary set
When b0-00 is set to 2, the switch between master frequency set, and auxiliary frequency set
can be realized through digital input terminal "frequency set switchover". When terminal
"frequency set switchover" is invalid, frequency set of the drive will be determined by b0-01.
When terminal "frequency set switchover" is valid, frequency set of the drive will be
determined by b0-03 (Auxiliary frequency set source).
3: Switch between master FREQ set, and master & auxiliary computation result
When b0-00 is set to 3, frequency is determined by master frequency set, or master &
auxiliary computation result through digital input terminal "frequency set switchover". When
terminal "frequency set switchover" is invalid, frequency is determined by b0-01 (master
frequency set source). When terminal "frequency set switchover" is valid, frequency is
determined by master & auxiliary computation result. The master & auxiliary computation
relation is determined by b0-07.
4: Switch between auxiliary FREQ set, and master & auxiliary computation result
When b0-00 is set to 4, frequency is determined by auxiliary frequency set, or master &
auxiliary computation result through digital input terminal “frequency set switchover”. When
terminal "frequency set switchover" is invalid, frequency is determined by b0-03 (auxiliary
frequency set source). When terminal "frequency set switchover" is valid, frequency is
determined by master & auxiliary computation result. The master & auxiliary computation
relation is determined by b0-07.
b0-01
Master frequency set
Range: 0~9
Factory default:
0
0: Digital setting (b0-02) +
∧
/
∨
adjustment on control panel
When the drive is powered up, the value of b0-02 is taken as the master frequency set which
can be adjusted through
∧
/
∨
keys on control panel no matter the drive is running or in
stop.