Chapter 5 List of Parameters GK600 User Manual
- 84 -
Parameter
Designation
Scope
Factory
default
Attr
C2-09
Input of curve 2 inflection
point B
Range: Curve 2 minimum input ~
Input of curve 2 inflection point A
0.0%
△
C2-10
Set value corresponding to
input of curve 2 inflection
point B
Range: -100.0%~100.0%
0.0%
△
C2-11 Curve 2 minimum input
Range: -110.0%~ input of curve 2
inflection point B
0.0%
△
C2-12
Set value corresponding to
curve 2 minimum input
Range: -100.0%~100.0%
0.0%
△
C2-13 Curve 3 maximum input
Range: input of curve 3 inflection
point A ~110.0%
100.0%
△
C2-14
Set value corresponding to
curve 3 maximum input
Range: -100.0%~100.0%
100.0%
△
C2-15
Input of curve 3 inflection
point A
Range: input of curve 3 inflection
point B ~ curve 3 maximum input
0.0%
△
C2-16
Set value corresponding to
input of curve 3 inflection point A
Range: -100.0%~100.0%
0.0%
△
C2-17
Input of curve 3 inflection
point B
Range: curve 3 minimum input~ input
of curve 3 inflection point A
0.0%
△
C2-18
Set value corresponding to
input of curve 3 inflection point
B
Range: -100.0%~100.0%
0.0%
△
C2-19 Curve 3 minimum input
Range: -110.0%~ input of curve 3
inflection point B
0.0%
△
C2-20
Set value corresponding to
curve 3 minimum input
Range: -100.0%~100.0%
0.0%
△
C2-21 AI1 terminal filtering time 0.000s~10.000s
0.1s
△
C2-22 AI2 terminal filtering time 0.000s~10.000s
0.1s
△
C2-23
EAI terminal filtering time
(on IO option board)
0.000s~10.000s
0.1s
△
C2-24 DI maximum input
Range: C2-26~50.0kHz
50.0kHz
△
C2-25
Set value corresponding to
DI maximum input
Range: -100.0%~100.0%
100.0%
△
C2-26 DI minimum input
Range: 0.0kHz~C2-24
0.0kHz
△
C2-27
Set value corresponding to
DI minimum input
Range: -100.0%~100.0%
0.0%
△
C2-28 DI filtering time
0.000s~1.000s
0.001s
△