Chapter 4 Operation and Run Instructions GK600 User Manual
- 68 -
Set the value in hundreds place:
As shown in Fig. 4-14, the parameter required to display does not involve hundreds place, so
the hundreds place shall be set to zero.
Set thousands place:
As shown in Fig. 4-14, since required to display "running linear speed" and "setting linear
speed", the binary set value of thousands place shall be 0011 that corresponds to 3 in a
hexadecimal number.
To sum up, L1-02 should be set to 3013.
Fig. 4-14 Setting of hexadecimal parameter L1-02
Under parameter setting status, the parameter value cannot be modified if the value has no
flashing digit. Possible causes include:
1) The parameter cannot be modified, such as actual detection parameters, running recording
parameters, etc;
2) This parameter cannot be modified in run status but can be changed when motor stopped;
3) Parameter under protection. When parameter A0-02 is set to 1, parameters cannot be
modified as the parameter protection against misoperation enabled. To edit parameter in
such a circumstance, it is necessary to set A0-02 to 0 as first step.
4.1.4.4 Lock/Unlock Control Panel
Lock control panel
All or some keys of CONTROL PANEL can be locked by any of the following three
methods. See the definition of parameter L0-01 for further information.
Method 1: set the parameter value of L0-01 to non-zero, then press
+
+
simultaneously.
Method 2: do not operate CONTROL PANEL within five minutes after L0-01 is set to
non-zero.
Method 3: cut the power off and then apply power on after L0-01 parameter is set to
non-zero.
Refer to flow chart 4-15 for locking CONTROL PANEL.
Unlock control panel
To unlock the control panel, press
+
+
simultaneously. Unlocking
won‟t change the value of parameter L0-01. In other words, the control panel will be locked