parameter value of E1-05, the drive will display overload fault and coast to stop.
E1-04
Overload alarm threshold
Range: 20.0%~200.0%
Factory default:
130.0%
When tens place of E1-03 is set to 0, this parameter value is a percentage compared to rated
current of motor. When tens place of E1-03 is set to 1, this parameter value is a percentage
compared to rated current of drive.
E1-05
Overload alarm activation
time
Range: 0.1s~60.0s
Factory default:
5.0s
Sets the lasting time that overload alarm is activated when output current of drive is bigger than
the threshold set by E1-04.
E1-06
Protection action 1
Range: 0000~1111
Factory default:
0000
E1-07
Protection action 2
Range: 0000~3111
Factory default:
3001
These two parameters set the protection action of the drive in the following abnormal status.
Specification of E1-06:
Ones place: reserved
Tens place: temperature measurement circuit fault (OH3)
0: Coast to stop
1: Alarm but run continued
Hundreds place: abnormal EEPROM (EPr)
0: Coast to stop
1: Alarm but run continued
Thousands place: abnormal terminal communication (TrC)
0: Coast to stop
1: Alarm but run continued
Specification of E1- 07:
Ones place: abnormal power supply when running (SUE)
0: Coast to stop
1: Alarm but run continued
Tens place: current detection circuit failed (CtC)
0: Coast to stop
1: Alarm but run continued
Hundreds place: abnormal contactor (CCL)
0: Coast to stop
1: Alarm but run continued