GK600 User Manual
Chapter 6 Specification of Parameters
-
161 -
17: Drive overheat alarm
When drive internally detected temperature exceeds E1-13 (Drive overheat alarm
threshold), ON signal will be output.
18: Zero-current detection
When drive output current is less than the value of C1-15 (effective proportion of zero
current detected) and the lasting time attains the value of C1-16 (Zero current detected
time), ON signal will be output.
19: X1
Output the status of X1.
20: X2
Output the status of X2.
21: Motor 1/2 indication
When motor 1 is selected, outputs OFF. When motor 2 is selected, outputs ON.
22: Set count value attained
Refer to the specification of parameter F3-12.
23: Designated count value attained
Refer to the specification of parameter F3-13.
24: Length attained
Refer to the specification of parameters F3-08~F3-11.
25: Consecutive run time attained
When consecutive run time attains the value of E0-03, corresponding terminal outputs ON.
Consecutive run time is cleared when stop.
26: Accumulative run time attained
When accumulative run time attains the value of E0-04, corresponding terminal outputs ON.
Accumulative run time is maintained when stop.
27: Brake control
Refer to the specification of parameters E0-05~E0-11 for details.
28: Reserved
29: Reserved
30: PLC step completed
Upon the completion of current step of simple PLC running, ON signal with the width of
500ms will be output.
31: PLC cycle completed
Upon the completion of a cycle of simple PLC running, ON signal with a width of 500ms will
be output.
32: Wobble frequency attains to upper or lower limit frequency
When drive output frequency attains upper limit frequency b0-09 or lower limit frequency
b0-10 under wobble frequency running, ON signal will be output.
33: Upper/lower limit of set FREQ attained
34: Target FREQ attained (set by C2-29)
When the error of drive output frequency and C2-29 value is less than C1-14, target