GK600 User Manual
Chapter 5 List of Parameters
- 81 -
Parameter
Designation
Scope
Factory
default
Attr
1: Maintained
Hundreds place: integral function
0: No integral function
1: Integral function enabled
Thousands place: run direction
0: Changing run direction prohibited
1: Changing run direction allowed
C0-18
Terminal UP/DOWN
frequency change step size
0.00Hz/s~100.00Hz/s
0.03 Hz/s
△
C0-19
FWD/REV terminal control
mode
0: Two-wire mode 1
1: Two-wire mode 2
2: Three-wire mode 1
3: Three-wire mode 2
0
×
C0-20
Option of virtual input
terminal
000~77F
0: Actual terminal in effect
1: Virtual terminal in effect
Ones place: BIT0~BIT3: X1~X4
Tens place: BIT4~BIT6: X5~X6, EX
Hundreds place: BIT8~BIT10:
AI1~AI2, EAI (EX and EAI located at
IO option board)
000
×
C0-21
Enabled condition of run
command terminal after
fault reset (RESET)
0: Trigger edge de ON
detected
1: ON detected
0
△
Group C1 Digital Output
C1-00 Y1 output function
0: No output
1: Drive undervoltage
2: Drive run preparation completed
3: Drive is running
4: Drive running at 0Hz (there is no
output at stop)
5: Drive running at 0Hz (there is
output at stop)
6: Run direction
7: FREQ attained
8: Upper limit FREQ attained
9: Lower limit FREQ attained
10: Frequency detection FDT1
11: Frequency detection FDT2
12: Reserved
13: Torque limited
0
△
C1-01
Y2/DO output function
(when used as Y2)
0
△
C1-02
Control board relay output
function
14
△
C1-03
Option board relay output
function
15
△