Group F2 Simple PLC
Simple PLC is a multi-step frequency generator. The drive can automatically change run
frequency and direction based on the run time so as to meet on-site technological requirements.
Flow chart is shown as Fig. 6-49.
Fig. 6-49
a0~a15 are the Accel times of steps, while d0~d15 are the Decel times.
f0~f15 are the set frequencies of steps while T0~T15 are the run times.
Upon the completion of current step of simple PLC, digital output terminal "PLC step
completed" outputs ON signal, 500ms. When simple PLC finishes a run cycle, digital output
terminal "PLC cycle completed" outputs ON signal, 500ms.
F2-00 Simple PLC run mode
Range: 0000~1212
Factory default:
0000
Ones place: PLC run mode
0: Stop after a single cycle
PLC stops upon the completion of one cycle and it won‟t be started unless another run
command is given, shown as Fig. 6-50.