Chapter 6 Specification of Parameters GK600 User Manual
- 146 -
If run command terminal is in ON state before power up, the drive will not run after power up.
Under this circumstance, only when the ON state is shifted to OFF and then ON again, and
maintain ON, the drive will start running.
1: ON detected
When run command is controlled by terminals, the drive will start to run when detecting the
command terminal at ON state after power up.
ATTENTION:
When “1: ON detected” selected, the drive will start to run after power up as long as ON of
run command terminal detected. Make sure of the safety of personnel and equipment before
this setting.
C0-01 Function of terminal X1
Range: 0~99
Factory default: 0
C0-02 Function of terminal X2
Range: 0~99
Factory default: 0
C0-03 Function of terminal X3
Range: 0~99
Factory default: 0
C0-04 Function of terminal X4
Range: 0~99
Factory default: 0
C0-05 Function of terminal X5
Range: 0~99
Factory default: 0
C0-06 Function of terminal X6/DI
Range: 0~99
Factory default: 0
C0-07
Function of terminal EX
(on IO option board)
Range: 0~99
Factory default: 0
C0-08
Function of terminal AI1 (Digital
enabled)
Range: 0~99
Factory default: 0
C0-09
Function of terminal AI2 (Digital
enabled)
Range: 0~99
Factory default: 0
C0-10
Function of terminal EAI (Digital
enabled) (on IO option board)
Range: 0~99
Factory default: 0
Analog input terminals AI1, AI2 and EAI can also be used as digital input terminals set by
C0-08~C0-10. When AI1, AI2 and EAI are used as analog input, C0-08~C0-10 shall be set to 0.
Parameter setting of digital input is as shown in Table 6-6:
Table 6-6 Digital input functions
Set value Function
Set value Function
0
No function
26
Reserved
1
JOG forward
27
Run command switched to
control panel control
2
JOG reverse
28
Run command switched to
terminal control
3
Run forward (FWD)
29
Run command switched to
communication control