GK600 User Manual
Chapter 6 Specification of Parameters
-
193 -
d4-11
Drooping FREQ of droop
control
Range: 0.00Hz~maximum
frequency
Factory default:
0.00Hz
d4-12 Current limitation source
Range: 0~5
Factory default: 1
d4-13
Digital setting of current
limit value
Range: 20.0%~200.0%
Factory default:
160.0%
d4-14
Flux weakening current
limit coeff
Range: 0.001~1.000
Factory default:
0.500
d4-15 Energy saving percentage Range: 0.0%~40.0%
Factory default:
0.0%
d4-16
V/f oscillation suppression
gain 1
Range: 0~3000
Factory default:
38
d4-17
V/f oscillation suppression
gain 2
Range: 0~3000
Factory default: 0
d4-18
Voltage setting on V/f
separated pattern
Range: 0~5
Factory default: 0
d4-19
Digital set voltage on V/f
separated pattern
Range: 0.0%~100.0%
Factory default:
0.0%
d4-20
Voltage variation time on
V/f separated pattern
Range: 0.00s~600.00s
Factory default:
0.01s
Group d5 Vector Control Parameters of Motor 2
Set control parameters in Group d5 when motor 2 is selected as current load motor on which
SVC is performed. The specification of SVC parameters of motor 2 in Group d5 is exactly the
same with that of SVC parameters of motor 1 in Group d3.
d5-00 Reserved
Reserved
Reserved
d5-01
ASR high-speed
proportional gain Kp1
Range: 0.0~20.0
Factory default:
2.0
d5-02
ASR high-speed
integration time Ti1
Range: 0.000s~8.000s
Factory default:
0.200
d5-03
ASR low-speed
proportional gain Kp2
Range: 0.0~20.0
Factory default:
2.0
d5-04
ASR low-speed integration
time Ti2
Range: 0.000s~8.000s
Factory default:
0.20
d5-05
ASR switching frequency 1
Range: 0.00Hz~d5-06
Factory default:
5.00Hz
d5-06
ASR switching frequency 2 Range: d5-05~upper limit
frequency
Factory default:
10.00Hz