GK600 User Manual
Chapter 5 List of Parameters
- 75 -
Parameter
Designation
Scope
Factory
default
Attr
5: X6/DI pulse input
6: Process PID output
7: PLC
8: Multi-step speed
9: Communication
b0-02 Master FREQ digital setting Lower limit freq ~ upper limit freq
50.00Hz
△
b0-03 Auxiliary FREQ set
0: No setting
1: Digital setting (b0-04) +
∧
/
∨
adjustment on control panel
2: Digital setting (b0-04) + terminal
UP/DOWN adjustment
3: Analog input AI1
4: Analog input AI2
5: Analog input EAI (on IO option
board)
6: X6/DI pulse input
7: Process PID output
8: PLC
9: Multi-step speed
10: Communication
0
×
b0-04
Auxiliary FREQ digital
setting
Lower limit FREQ ~ upper limit FREQ 0.00Hz
△
b0-05 Auxiliary FREQ range
0: Relative to maximum FREQ
1: Relative to master FREQ
0
×
b0-06 Auxiliary FREQ coeff
0.0%~100.0%
100.0%
×
b0-07
Computation of master and
auxiliary FREQ
0: auxiliary
1: Master - auxiliary
2: Max {master, auxiliary}
3: Min {master, auxiliary}
0
×
b0-08 Maximum FREQ
Upper limit FREQ ~600.00Hz
50.00Hz ×
b0-09 Upper limit FREQ
Lower limit FREQ ~ maximum FREQ 50.00Hz ×
b0-10 Lower limit FREQ
0.00Hz~upper limit FREQ
0.00Hz
×
b0-11
Operation when set FREQ
lower than lower limit
FREQ
0: Run at lower limit FREQ
1: Run at 0 Hz
2: Stop
0
×
b0-12
Time-delay of stop when
set FREQ lower than lower
limit FREQ
0.0s ~ 6553.5s
0.0s
×
b0-13
Lower limit of skip FREQ
band 1
0.00Hz~upper limit FREQ
0.00Hz
×
b0-14
Upper limit of skip FREQ
band 1
0.00Hz~upper limit FREQ
0.00Hz
×