GK600 User Manual
Chapter 3 Installation and Wiring
- 23 -
Chapter 3 Installation and Wiring
3.1 Installation Environment
1
)
Ambient temperature is in the range of -10
℃
~ 40
℃
.
2
)
Drive should be installed on surface of flame retardant object, with adequate surrounding
space for heat dissipation.
3
)
Installation should be performed where vibration is less than 5.9m/s
2
(0.6g).
4
)
Protect from moisture and direct sunlight.
5
)
Protect the cooling fan by avoiding oil, dust and metal particles.
6
)
Do not expose to an atmosphere with flammable gases, corrosive gases, explosive gases
or other harmful gases.
7
)
Prevent drilling residues, wire ends and screws falling into drive.
8
)
Ventilation part of the drive should be installed outside from harsh environment (e.g. textile
facilities with fiber particles and chemical facilities filled with corrosive gases).
3.2 Minimum Mounting Clearances
To ensure favorable heat dissipation, mount the drive upright on a flat, vertical and level surface
as per Fig. 3.1. For installation inside cabinet, the product shall be mounted side by side to the
greatest extent while adequate surrounding space shall be preserved for favorable heat
dissipation.
Fig. 3-1 Minimum mounting clearances of GK600-2T7.5B and below, GK600-4T15G/18.5LB
and below
空气流通位置
100mm
100mm
空气流通位置
30mm
30mm
Vent clearance
Vent clearance