Chapter 6 Specification of Parameters GK600 User Manual
- 196 -
parameter takes effect only for V/f control, while over-modulation is enabled all the time
under SVC pattern.
Thousands place: PWM switching FREQ relation with output frequency
0: Self-adaption
1: No adaption
When this bit is set to 0, the drive running at low speed automatically reduces its switching
frequency, so as to improve the motor load carrying capacity at low speed. Please set this
bit to 1 if PWM switching frequency change is not allowed.
E0-02
Action when run time
attained
Range: 000~111
Factory default:
000
Ones place: action when consecutive run time attained
0: Run continued
When the drive consecutive run time attains the set value of E0-03, the drive will continue to
run.
1: Stop and fault reported
When the drive consecutive run time attains the set value of E0-03, the drive will report fault
code "to2" and coast to stop. Digital output terminal "consecutive run time attained" will
output ON. When E0-03 is set to 0, this parameter value is enabled.
Tens place: action when accumulative run time attained
0: Run continued
When the drive accumulative run time attains the set value of E0-04, the drive will continue to
run.
1: Stop and fault reported
When the drive accumulative run time attains the set value of E0-04, the drive will report fault
"to3" and coast to stop. Digital output terminal "accumulative run time attained" will output
ON. When E0-04 is set to 0, this parameter value is enabled.
Hundreds place: unit of running time:
0: Second
1: Hour
Sets the unit of E0-03 consecutive run time and E0-04 accumulative run time.
E0-03
Consecutive run time
setting
Range: 0.0~6000.0s(h)
Factory default:
0.0 s(h)
When consecutive run time attains this set value, the drive will perform the action set by ones
place of E0-02. Time unit is set at hundreds place of E0-02. When this parameter value is set to
0, this function is enabled.
E0-04
Accumulative run time
setting
Range: 0.0~6000.0s(h)
Factory default:
0.0 s(h)
When accumulative run time attains this set value, the drive will perform the action set by tens